  1. Portable fire extinguishers of approved type 2A:20-B:C and suitable for the hazards and circumstances should be provided throughout the property and located so an extinguisher is within 50 feet of any point. A minimum of two, 4- A:40-B:C, should be located outside of and within 30 feet of each fuel pump and in clear view in the gas dock area. These fire extinguishers should be placed at least 15 feet apart, if possible. Fire extinguishers should be inspected monthly.
  2. The gasoline dispensing and other areas where flammable materials are stored or used should be posted as outlined in NFPA 303 (Fire Protection Standards for Marinas and Boatyards) or NFPA 307 (Standard for the Construction and Fire protection of Marine Terminals, Piers and Wharves) as applicable.
  3. A clearly identified and readily accessible emergency switch that can be used to shut off the supply of power to gasoline pumps should be located on land and near the dispensing pumps should a leak develop.
  4. At least one Coast Guard approved throw-type flotation device (with at least 60 feet of ¾-inch diameter rope attached or a reach pole) should be located in clear view on the gas dock and every 200 feet on other docks.
  5. Immediate notification to the nearest fire department in the event of fire should be the established operating procedure. An approved means for sounding an alarm to notify yard personnel and others of a fire on the premises should be provided.
  6. All fire extinguisher locations should be clearly marked and within easy access. Fire extinguishers should be inspected monthly to ensure they operate properly, when needed.
  7. Emergency phone numbers should be posted conspicuously near the telephone.
  8. Combustible waste material and residues should be kept to a minimum, stored in covered metal receptacles, and disposed of daily as specified in NFPA 303.
  9. National Fire Protection Codes should be consulted for specific details.
  10. Local fire department personnel should be invited to inspect the facility, at least annually, with special emphasis on access to different areas of the marina in order to fight a fire.
  11. Marina staff should have firefighting training and drill at least twice a year as specified in NFPA 303.
  12. A safety skiff should be available and ready for use. The skiff should be equipped with a wire rope and an attached grapple hook. This skiff should be used to tow a vessel that may be on fire to open water and away from other craft or structures.

Current Issue

Current Issue of Marine Construction Magazine

Advertisement

Additional Stories

Let’s Talk Safety: Workbench Grinder Wheel Explodes, One Dead

Let’s Talk Safety: Workbench Grinder Wheel Explodes, One Dead

A mechanic needed a work bench mounted grinder and went to the

CASE STUDY: Loudoun Water Adopts Digital Asset Management

CASE STUDY: Loudoun Water Adopts Digital Asset Management

Located in Northern Virginia near Washington, D.C., Loudoun Water provides drinking water

New Holland Construction Commercially Releases the C330 Super Boom Vertical Lift Compact Track Loader

New Holland Construction Commercially Releases the C330 Super Boom Vertical Lift Compact Track Loader

New Holland’s C330 Super Boom vertical lift compact track loader is now

Let’s Talk Safety: Problem gas well contacts ignition source, explosion kills five

Let’s Talk Safety: Problem gas well contacts ignition source, explosion kills five

Employees #1 through #5 were crew members on a barge-mounted drilling rig